Overview
The iTrixx-Ultra 300-C is a wired equipment hour meter kit that pairs an iTrixx-Ultra 300 Ethernet controller with a clamp-on current sensor, so you can monitor a machine’s on/off runtime simply by clamping the sensor around its AC power wire — no wiring changes needed. When current crosses your preset threshold, the meter counts, and the dual meters let you separate powered-on uptime from active runtime. It’s a reliable machine hour meter for generators, water pumps, semiconductor machines, and other equipment where a clean trigger source is hard to find. With its built-in task builder you can set up to 32 conditions to watch energy use, catch overloads, and fire alerts, and with MQTT and encryption support it drops into a secure data pipeline. An affordable, secure equipment hour meter.
How It Works
- Mount the meter on or near your equipment and choose how it counts: by power input (wire it to the same power source as the equipment — when it’s powered, it’s counting), by digital/analog input (a 5–24VDC sensor or a current sensor detects the on/off state), or by relay output (the meter follows a relay).
- Connect the meter to your network — Ethernet by cable, or WiFi with a quick browser/Telnet setup.
- Install the free HourCollector desktop or mobile app. The meter reports its runtime automatically and the app saves it to a CSV file for history and reporting.
- Set scheduled email reports and maintenance alerts — you’ll get a notification or an audible/visual alert when a machine is due for service.
What’s in the Box
- iTrixx-Ultra 300 SERVER
- 1A 12V power supply
- Current sensor
- **Specifications**
- Power Requirements: Power Input: 5-48 VDC
- Relay Outputs: Numbers of relay output: 2, Dry contact, signal Relay,2 Form C, 1A @ 30VDC
- Digital Inputs: Numbers of digital input: 2,
- Two modes of operation for the digital inputs:
- Isolated mode (ISO): 5-24VDC@30mA max
- PULL UP mode (PU): used with a switch to activate a signal
- Analog Inputs: Numbers of analog input: 2, isolated 2-wire input: voltage: 5V or current 4-20mA
- Real-Time Clock
- NTP automatic Internet time setting
- NTP Sync Period: User settable
- Automatic Daylight Savings Adjustment
- Battery (capacitor) Power Backup
- Capacitor Power Backup
- Backup Functions: Retain Real-Time Clock, basic settings
- Backup Duration: 2 weeks minimum
- Network
- Type: 10/100 Base-TX POE Ethernet Port
- POE: IEEE 802.3af
- Setup: Static or DHCP IP address configuration
- Connectors
- Power: Micro USB connector
- External temperature & humidity: Mini USB
- Network: RJ-45
- Relay output: Spring-cage pluggable terminal blocks, NC-C-NO
- Digital input: Spring-cage pluggable terminal blocks, C- A
- Analog input: Spring-cage pluggable terminal blocks, A – N
- CAN: H-L
- LED Indicators
- Number of LEDs: 5
- Pulse: Red, power on
- Boot: Green, boot mode
- Locate: Blue, device locator
- Network: Orange, network connected, green: activity
- Physical
- Operating Temperature: 0 to +70 Celsius
- Storage temperature from -40 to +125 Celsius
- Humidity from 10% to 90% non-condensing
- Dimensions: 70mm x 100mm x 25mm
- Weight: 11 oz
- Enclosure Material: POLYLAC® PA-765A Acrylonitrile Butadiene Styrene (ABS)
- Enclosure Flame Rating: UL94
- Protocols: DHCP, DNS, TCP/IP (IPv4), UDP, HTTP/HTTPs , MQTT, SSL, XML
- Email Notifications
- Encrypted Email Alerts: STARTTLS and TLSL/SSL
- Alert Functions: Fully customizable: alerts can be scheduled, or based on input/output data/state changed
- Logging
- Up to 10,000 downloadable logs
- Storage: Up to 2MB Flash memory (plus an additional 160 KB of Boot Flash)
- Current Sensor
- Input Current: 0-15A
- Output Type: 0-1V
- Opening size: 13mm*13mm
- Core material: Ferrite
- Mechanical strength: the number of switching is not less than 1000 times(test at 25°C)
- Safety index: dielectric strength (between sheel and output)6000V AC/1min
- Fire resistance property: in accordance with UL94-Vo
- Work temperature: -25°C – 70°C